A Pt100 sensor is a platinum resistance temperature detector (RTD) with a nominal resistance of 100 ohms at 0°C. It measures temperature by detecting changes in electrical resistance as the temperature rises or falls. Pt100 sensors are widely used in industrial equipment, including air compressors, for reliable temperature monitoring.

1. How Does a Pt100 Sensor Work?
A Pt100 sensor uses platinum as its sensing element. Platinum has a positive temperature coefficient (PTC), which means its electrical resistance increases as temperature rises.
At 0°C, the nominal resistance is 100 ohms. As the temperature changes, the sensor’s resistance follows a standardized resistance-temperature relationship defined by IEC 60751.
A controller or temperature transmitter measures this resistance and converts it into a temperature reading.

Pt100 Resistance at Different Temperatures
| Temperature | Approximate Resistance |
|---|---|
| 0°C | 100.00 Ω |
| 25°C | 109.73 Ω |
| 50°C | 119.40 Ω |
| 100°C | 138.51 Ω |
These values follow the standard Pt100 curve with a temperature coefficient of 0.00385.
2. What Are the Different Pt100 Wiring Configurations?
Pt100 sensors commonly use three wiring configurations: 2-wire, 3-wire, and 4-wire. Each configuration affects measurement accuracy and installation requirements.
2-Wire Pt100
A 2-wire connection uses two wires to connect the sensor to the measuring device. It offers simple installation but includes lead-wire resistance in the measurement, which can reduce accuracy.
3-Wire Pt100
A 3-wire connection compensates for most lead-wire resistance when the connecting wires have similar resistance. It offers a practical balance between measurement accuracy and installation cost, making it common in industrial applications.
4-Wire Pt100
A 4-wire connection separates the current and voltage measurement paths. This arrangement minimizes lead-wire resistance errors and supports more accurate temperature measurements.
3. What Affects Pt100 Sensor Accuracy?
Several factors influence Pt100 measurement accuracy:
- Accuracy class: Class AA, A, and B sensors have different tolerance limits.
- Wiring configuration: Lead-wire resistance can affect the measured temperature, especially in 2-wire circuits.
- Installation: Poor thermal contact or incorrect probe placement can cause measurement errors.
- Operating conditions: Vibration, moisture, and mechanical stress can affect sensor performance and service life.
For industrial applications, check the sensor’s accuracy class and installation requirements rather than relying on the Pt100 designation alone.
4. Where Are Pt100 Sensors Used in Air Compressors?
Pt100 sensors help monitor temperatures in industrial equipment and air compressor systems. Depending on the compressor design, they may measure:
- Discharge air temperature to monitor heat generated during compression.
- Lubricating oil temperature to help monitor operating conditions.
- Cooling system temperature to support thermal management.
- Other critical temperature points specified by the compressor manufacturer.
Accurate temperature monitoring helps operators identify abnormal operating conditions and maintain stable compressor performance.
5. How Do You Choose the Right Pt100 Sensor?
Before purchasing a replacement Pt100 sensor, check the following specifications:
- Resistance type: Confirm that the original sensor uses Pt100 rather than Pt1000.
- Accuracy class: Check whether the application requires Class AA, A, or B.
- Wiring: Confirm the 2-wire, 3-wire, or 4-wire configuration.
- Probe dimensions: Check probe length, diameter, and mounting connection.
- Temperature range: Make sure the sensor supports the required operating conditions.
- Controller compatibility: Verify the input specifications of the compressor control system.
If you need a replacement, explore our Pt100 temperature sensor product details to check available specifications and find a suitable option for your air compressor.
FAQ
What does Pt100 stand for?
Pt stands for platinum, and 100 refers to its nominal resistance of 100 ohms at 0°C.
What is the normal resistance of a Pt100 sensor?
A standard Pt100 has 100 ohms at 0°C. Its resistance increases as temperature rises.
Is Pt100 a thermocouple or an RTD?
Pt100 is an RTD (Resistance Temperature Detector), not a thermocouple. It measures temperature through changes in electrical resistance.
Can I replace a Pt100 sensor with a Pt1000?
Not directly. The compressor controller must support Pt1000 inputs, so always check the original sensor specification and controller compatibility before replacement.